BHU Windows, Lighting and Ventilation Requirements: Window Size, Windowless Toilets and Air-Conditioners
By Holling One-Stop BHU Certification | Last updated: 24 November 2026
Short answer
- Start with the Building (Planning) Regulations: if a room already meets the natural lighting and ventilation requirements of regulations 30 to 33 (habitable rooms) or 36 (toilets), it complies.
- If not, use the BHU requirements: every habitable space needs at least one openable window facing the outdoors (glazed area at least 0.1 m²), plus artificial lighting and mechanical ventilation with at least 5 air changes per hour using outdoor air.
- Air-conditioners do not count as mechanical ventilation: window or ceiling exhaust fans with ducting do.
- Toilets: artificial lighting and mechanical ventilation with 5 air changes per hour; a toilet without a window also needs permanent ventilation of at least 1/20 of its floor area.
Summarised from paragraph 4.8 of the Government’s Code of Practice on the Minimum Standards of Living Conditions for BHUs. Lighting and ventilation is one of the eight BHU minimum standards.

Habitable spaces: how big must the window be, and where must it face?
| Item | Requirement |
|---|---|
| Number of windows | At least one openable window per habitable space |
| Glazed area | At least 0.1 m² |
| Facing | The outdoors: an open street, service lane, courtyard or light well (including semi-enclosed or fully enclosed light wells) |
| Hung windows | The sash must open at least 0.6 m, or the sash height if shorter |
| Artificial lighting | Required |
| Mechanical ventilation | At least 5 air changes per hour using outdoor air; exhaust fans and ducting count, air-conditioners do not |
What if the window opens onto a light well?
- The light well must be uncovered and unobstructed above;
- its horizontal dimension must be at least 1.5 m;
- if fully enclosed, it must have at least 1 m² of horizontal area for every 6 m of wall height;
- for a fully enclosed light well, there must be access at its lowest level for cleaning and maintenance (in common parts or private premises).
Light wells in older buildings are often covered or obstructed by additions. If a light well has an unauthorised roof, the window may not count as facing the outdoors, so check this at assessment. Unauthorised structures in light wells are also outside the BHU regime; see Building Department Orders and BHU Recognition.
Can a room without a window be a BHU?
Every habitable space must have at least one openable window facing the outdoors. A windowless room generally needs the layout to be changed, for example by reallocating rooms so every habitable space has a window, or by using the space for a non-habitable purpose. This often affects how many units the flat can hold, so deal with it at assessment.
Toilets and windowless toilets
| Situation | Requirement |
|---|---|
| All separate toilets | Artificial lighting + mechanical ventilation with at least 5 air changes per hour using outdoor air (exhaust fans and ducting count, air-conditioners do not) |
| Natural lighting and ventilation not met (e.g. windowless toilet) | Also permanent ventilation connected to an open street, service lane, courtyard, light well or another room with a window, through a duct with cleaning access or a suitably placed vent in a wall or door, permanently open or louvred, with an area of at least 1/20 of the toilet floor area |
For example, a 2 m² windowless toilet needs a permanent vent of at least 0.1 m² (2 ÷ 20). For other toilet requirements, see BHU Toilet and Sink Requirements.
What about kitchens?
If an SDU has a kitchen, it must meet the kitchen natural lighting and ventilation requirements of regulations 30 and 31 of the Building (Planning) Regulations, or the habitable-space requirements in paragraph 4.8.2. Open-flame cooking has separate fire safety limits; see BHU Fire Safety Requirements.
FAQ
Does an air-conditioner count as mechanical ventilation?
No. The Code of Practice states that air-conditioners are not regarded as mechanical ventilation; window or ceiling exhaust fans with ducting are.
What is the minimum window size for a BHU?
A glazed area of at least 0.1 m², openable and facing the outdoors, such as a street, service lane, courtyard or a light well meeting the size requirements.
Can a windowless toilet be part of a BHU?
Yes, with artificial lighting, mechanical ventilation at 5 air changes per hour, and permanent ventilation of at least 1/20 of the toilet floor area.
How are 5 air changes per hour calculated?
The exhaust equipment must remove at least five times the room’s volume of air every hour. For example, a 10 m³ toilet needs a fan extracting at least 50 m³ per hour; allow for airflow losses in ducting and have a professional size it on site.