BHU Fire Safety Requirements: Partitions, Fire Doors and Fire Detectors (3 Scenarios Explained)
By Holling One-Stop BHU Certification | Last updated: 23 November 2026
Short answer: what do BHU fire safety rules look at?
- Start with the original entrance fire door: whether the flat (the “host flat”) keeps its original entrance fire door determines how wide the corridor must be and what fire resistance the room doors and partitions need.
- Corridor width: if the original fire door is kept, the common corridor must be at least 0.75 m clear; if it has been removed or is inadequate, at least 1.05 m.
- Equipment: at least one stand-alone fire detector in each SDU and in the common area; a dry powder extinguisher of 5 kg or more in the common area; installed by a registered fire service installation contractor who issues an FS251, then inspected every 12 months.
- Cooking: no open-flame cooking appliances in SDUs or common areas unless a compliant separate enclosed kitchen is provided.
Summarised from paragraph 4.4 of the Government’s Code of Practice on the Minimum Standards of Living Conditions for BHUs. Fire safety is one of the eight BHU minimum standards.
Basic requirements for means of escape
- Unless the building only has one staircase, an SDU must have access to at least two escape staircases.
- Corridor clear width is measured between the finished wall surfaces; shoe cabinets, storage and extinguishers must not reduce it below the requirement.
- Corridor clear headroom must be at least 2 m.
3 scenarios: does keeping the original fire door make a difference?
Scenario 1: the flat’s original entrance fire door is kept
Applies where the original entrance fire door remains, or has been replaced with one of equal or higher fire resistance, and an internal common corridor leads to the SDUs.
- Common corridor at least 0.75 m clear; at least 0.85 m if the host flat accommodates 31 to 200 persons.
- Each SDU entrance has a self-closing door with smoke seals.
- Walls between the corridor and the SDUs, and between SDUs, must be solid non-combustible partitions running from floor to ceiling.
Scenario 2: the original fire door has been removed or replaced with an inadequate door
- Common corridor at least 1.05 m clear.
- Each SDU entrance door must have a fire resistance rating of at least 1 hour and be self-closing with smoke seals.
- The relevant walls must also have at least 1-hour fire resistance and smoke-stopping performance.
In older buildings, the original front door has often been replaced with an ordinary metal gate or timber door, and the corridor is less than 1.05 m. There are generally two options: reinstate a compliant fire door (back to scenario 1), or re-plan the partitions so the corridor reaches 1.05 m and upgrade the doors and walls to 1-hour fire resistance. The effect on layout, room sizes and works differs, so the options should be compared after measuring on site.
Scenario 3: SDU entrances open directly onto the building’s common corridor
If SDUs open directly onto the building’s common corridor rather than an internal corridor, the entrance doors and the walls between SDUs must meet the 1-hour fire resistance and smoke-stopping requirements.
| Item | Scenario 1: original fire door kept | Scenario 2: original fire door removed or inadequate | Scenario 3: entrance onto building common corridor |
|---|---|---|---|
| Internal common corridor clear width | ≥ 0.75 m (31–200 persons: ≥ 0.85 m) | ≥ 1.05 m | N/A |
| SDU entrance door | Self-closing + smoke seals | ≥ 1-hour FRR, self-closing, smoke seals | ≥ 1-hour FRR, self-closing, smoke-stopping |
| Partitions | Solid non-combustible, floor to ceiling | ≥ 1-hour FRR and smoke-stopping | Between SDUs: ≥ 1-hour FRR and smoke-stopping |

Smoke-stop doors, fire doors, fire-rated partitions and non-combustible materials must comply with Part E of the Buildings Department’s Code of Practice for Fire Safety in Buildings 2011. During certification, the specified professional checks doors and walls and verifies fire and smoke performance through test or assessment reports or professional analysis, so keeping material documentation during the works is important.
How many fire detectors and extinguishers?
| Equipment | Number and location | Other requirements |
|---|---|---|
| Stand-alone fire detector | At least one in each SDU and at least one in the host flat’s common area; preferably on the ceiling | No connection to the building’s fire alarm system needed |
| Dry powder extinguisher | One per 100 m² of common area (less than 100 m² counts as 100 m²), 5 kg or more, FSD-approved | In a conspicuous, accessible position, without reducing corridor clear width |
These installations must be installed by a registered fire service installation contractor, who issues a Certificate of Fire Service Installations and Equipment (FS251). The owner or operator must then keep them in efficient working order and arrange an inspection by a registered contractor every 12 months.
Is open-flame cooking allowed in a BHU?
Open-flame cooking appliances (for example LPG or town gas stoves) are not allowed in SDUs or the host flat’s common areas. Open-flame cooking requires a separate enclosed kitchen complying with the Buildings Ordinance, or an open kitchen approved by the Buildings Department and Fire Services Department. Most conversions use induction hobs to avoid extra kitchen fire-protection works.
A real conversion example
Holling’s Wan Chai three-unit case shows how partitions, room doors and separate toilets were handled in an older building. See more in our portfolio, and our services for assessment, conversion and application support.
FAQ
Can timber or plasterboard partitions be used?
It depends on the scenario and material evidence. Scenario 1 requires solid non-combustible partitions from floor to ceiling; scenarios 2 and 3 require 1-hour fire resistance and smoke-stopping. Ordinary timber partitions generally do not comply; compliance depends on material test or assessment reports.
Do fire detectors need to connect to the building’s fire alarm?
No. The Code of Practice states that stand-alone fire detectors do not need to be connected to the building’s fire alarm system.
If I install fire detectors and extinguishers, does the unit meet the fire safety standard?
No. Equipment is only one part; corridor width, escape staircases, and the fire and smoke performance of doors and partitions must all comply.
What is an FS251?
An FS251 is the certificate issued by a registered fire service installation contractor after installing or inspecting fire service installations. BHU fire detectors and extinguishers must be installed by a registered contractor who issues an FS251, then inspected every 12 months.
Sources
- Government: Code of Practice on the Minimum Standards of Living Conditions for BHUs, paragraph 4.4 (fire safety)
- Basic Housing Units website: Basic Housing Unit Recognition (summary of minimum standards)
- Buildings Department: Guide on subdivided flats (Chinese; general fire safety requirements for subdivided flats)
This article is general information only. Actual requirements are subject to the Government’s Code of Practice and on-site certification by a specified professional.